Overview
ZW8-12 summus voltage vacuum circa ruptor velit, tres phase AC 50Hz altae voltage switchgear velit.Constat operandi, ambitus conductivi, systematis velitationis, sigilli et testae, et altiore structurae genus arcae communes tres phase.Ponitur pro 10kV rustica eget potentia et urbana potestas eget systematis potentiae, sicut split, onus current, onerare current, brevis circuitio current et alia similia loca.
Exsequendam vexillum GB1984-2003 "High Voltage AC Circuit Breaker" GB/T11022-1999 "Commune Technical Requirements for High Voltage Switchgear and Control Equipment Standards" IEC62271-100 "High Voltage AC Circuit Breaker"
Normalis usus Conditions
◆Ambiens temperatus: -40℃~+40℃;
◆Altitude: ≤3000m (si altitudo augetur, gradus insulationis aestimatus ergo crescet);
Aer circumfuso inquinari potest pulvere, fumo, vapore exedente, vapore vel imbre salso, et pollutio plana est IV;
◆ Celeritas venti non excedit 34m/s (aequivalet a 700Pa in superficie cylindrica);
◆Vibratio seu motus ab extra de commutatione et armorum potestate neglectus potest;
Special Conditions of use.(Si opus est ut sub ordinariis condicionibus usui a superioribus diversis adhiberetur, nobiscum negotiari placet).
Pelagus Technical Parametri
Serial numerus | Nomen | Unitas | Data | |
1 | Rated voltage | kV | 12 | |
2 | Ratum current | A | 630 1250 | |
3 | Potestas frequentiae siccum sustinere voltage (1min) | kV | 42 | |
4 | Fulmen impetus sustinere voltage (apicem) | 75 | ||
5 | Rated brevis-circuitu fractionis current | kA | 16 20 25 | |
6 | Rated brevis-circuitus faciens current |
| 40 50 63 | |
7 | Rated apicem sustinere current | kA | 40 50 63 | |
8 | 4s breve tempus sustinere current |
| 16 20 25 | |
9 | Operatio Nominal Sequentia |
| Puncta-0.3s-Combinatae puncta 18Os-Combinatae quaevis puncta | |
10 | Rated brevis-circuitu current temporibus fractionis | temporibus | 30 | |
11 | Mechanica vita | |||
Rated voltage of navitas repono motricium | temporibus | |||
12 | Rated voltage Opening coil operating | V | DCorAC 220 | |
Instructus speciali vere mechanismo operating claudendo coil | V | DCorAC 220 | ||
13 | Rated current of overcurrent release | A | 5 | |
14 | Licitum gerunt crassitudine static et dynamicae contactus | mm | 3 | |
15 | Contactus Spacing | mm | 11±1 | |
16 | Overtravel (compressionem ver longitudo contactum) | mm | +1.0 | |
17 | Tres polus clausurae et apertio diversorum temporum | ms | ≤2 | |
18 | Contactus claudendo REPENTE tempus | ms | ≤2 | |
19 | Mediocris ostium celeritas | m/s* | 1.0±0.2 | |
20 | Mediocris claudendo velocitate | m/s* | 0.7±0.15 | |
21 | foramen tempus | in summa operating voltage | s | 0.015-0.05 |
ad minimum operating voltage | s | 0.03-0.06 | ||
22 | cum claudendo | s | 0.025-0.05 | |
23 | Principalis circuitus resistentia | μΩ | ≤120 (cum G≤200) |